HTW ADMIRA -FST3-140ADM handleiding

192 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 73 van 192
b.
Using wire strippers, strip the rubber jacket
from both ends of the signal cable to reveal
approximately 15cm (5.9”) of wire.
c.
Strip the insulation from the ends.
d. Using a wire crimper, crimp u-lugs on the
ends.
NOTE: When connecting the wires, strictly
follow the wiring diagram found inside the
electrical box cover.
2.
Remove the electric cover of the outdoor unit.
3.
Connect the u-lugs to the terminals
Match the wire colors/labels with the labels
on the terminal block, Firmly screw the u-lug
of each wire to its corresponding terminal.
4.
Clamp down the cable with the cable clamp.
5.
Insulate unused wires with electrical tape.
Keep them away from any electrical or metal
parts.
6.
Reinstall the cover of the electric control box.
Indoor Unit Wiring
1. Prepare the cable for connection
a. Using wire strippers, strip the rubber jacket
from both ends of the signal cable to reveal
about 15cm (5.9”) of the wire.
b. Strip the insulation from the ends of the
wires.
c. Using a wire crimper, crimp the u-lugs to
the ends of the wires.
2. Undo the screw on the cover of the electric
control box and remove the cover.
3. Connect the u-lugs to the terminals.
Match the wire colors/labels with the labels
on the terminal block, Firmly screw the u-lug
of each wire to its corresponding terminal.
Refer to the Serial Number and Wiring
Diagram located on the cover of the electric
control box.
While connecting the wires, please strictly
follow the wiring diagram.
The refrigerant circuit can become very
hot. Keep the interconnection cable away
from the copper tube.
4. Clamp down the cable with the cable clamp.
The cable must not be loose or pull on the
u-lugs.
5. Reattach the electric box cover.
CAUTION
Outdoor Unit Wiring
WARNING
Before performing any electrical or wiring
work, turn off the main power to the
system.
1. Prepare the cable for connection
a.
You must first choose the right cable
size. Be sure to use H07RN-F cables.
Minimum Cross-Sectional Area of
Power and Signal Cables (For reference)
Rated Current of
Appliance (A)
Nominal Cross-Sectional
Area (mm²)
> 3 and 6
0.75
> 6 and 10
1
> 10 and 16
1.5
> 16 and 25
2.5
> 25 and 32
4
> 32 and 40
6
Cover
Screw
32