*Hotpoint models use R32 refrigerant. R32 is classified as a mildly flammable A2L refrigerant. At this time, some building codes restrict the use of products with
A2L refrigerants in some applications. These restrictions vary by location. Refer to all local building codes for guidance on acceptable use of Low GWP (A2L)
refrigerants for your application.
**All Hotpoint systems meet or exceed the 2025 CEE Split Air Source Heat Pump Specification and may qualify for the 2025 Energy Ecient Home Improvement
Credit (25C). For further information, please visit www.cee1.org.
© Copyright 2025 GE Appliances, a Haier Company.
Our continued commitment to quality products may mean a change in specifications without notice.
Pub No. 26-H2501 Rev. 06-20-2025
09K 12K 18K 24K
Model Number
Outdoor
1H09HN2DAB 1H12HN2DAB 1H18HN2DAB 1H24HN2DAB
UPC
084691980575 084691980582 084691980599 084691980605
Indoor
HW09HN2DAB HW12HN2DAB HW18HN2DAB HW24HN2DAB
UPC
084691980612 084691980629 084691980636 084691980643
Cooling
Capacity Range Btu/hr
3,100~11,000 3,300~13,800 4,100~20,000 4,700~25,200
SEER2
18 18 18 18
EER2
12 12 12 10.6
Rated Capacity 95°F Btu/hr
9,000 12,000 18,000 24,000
Moisture Removal Pt./h
1.0 1.2 2.2 2.4
Heating
Heating Capacity Range Btu/hr
2,100~11,000 2,800~13,300 3,800~20,000 4,300~25,600
HSPF2 (IV)
9.5 9.5 9.5 9.5
HSPF2 (V) 7. 2 7.1 7. 2 7.1
Rated Heating Capacity
47°F Btu/hr
10,000 13,000 19,000 25,000
Rated Heating Capacity
5°F Btu/hr
7,000 9,100 13,300 17,500
Max. Heating Capacity
5°F Btu/hr
7,000 9,100 13,300 17,500
COP@5F 1.8 1.8 1.8 1.8
Operating Range
Cooling °F (°C) 14~115°F (-10~46°C) 14~115°F (-10~46°C) 14~115°F (-10~46°C) 14~115°F (-10~46°C)
Heating °F (°C) -15~75°F (-26~24°C) -15~75°F (-26~24°C) -15~75°F (-26~24°C) -15~75°F (-26~24°C)
Power Supply
Voltage, Cycle, Phase V/Hz/-
208-230/60/1 208-230/60/1 208-230/60/1 208-230/60/1
Outdoor Unit
Compressor Type DC Inverter Rotary DC Inverter Rotary DC Inverter Rotary DC Inverter Rotary
Maximum Fuse Size A 15 15 20 25
Minimum Circuit Amp A 12 12 14 18
Basepan Heater Yes Ye s Yes Yes
Outdoor Noise Level dB 55 55 59 60
Dimension: Height in (mm) 21 3/4 (553) 21 3/4 (553) 25 1/4 (642) 25 1/4 (642)
Dimension: Width in (mm) 31 1/2 (800) 31 1/2 (800) 32 1/4 (820) 32 1/4 (820)
Dimension: Depth in (mm) 11 (280) 11 (280) 12 (306) 12 (306)
Weight (Net/Ship)- lbs (kg) 67.9/80.47 (30.8/36.5) 67.9/80.47 (30.8/36.5) 80.69/93.26 (36.6/42.3) 83.78/96.34 (38/43.7)
Indoor Unit
Fan Speed Stages 5 + Auto 5 + Auto 5 + Auto 5 + Auto
Maximum Indoor Sound Level (dB)
(Turbo/High/Med/Low/Quiet)
45/43/38/32/28 46/44/39/33/29 49/46/43/40/31 54/50/47/44/38
Dimension: Height in (mm) 11 (292) 11 (292) 12 1/8 (307) 13 5/8 (345)
Dimension: Width in (mm) 31 3/4 (805) 31 3/4 (805) 34 1/2 (875) 43 1/2 (1105)
Dimension: Depth in (mm) 7 7/8 (200) 7 7/8 (200) 8 1/2 (217) 9 1/2 (240)
Weight (Net/Ship)- lbs (kg) 18.74/24.47 (8.5/11.1) 18.74/24.47 (8.5/11.1) 21.83/28.22 (9.9/12.8) 32.63/41.67 (14.8/18.9)
Refrigerant Line
Refrigerant R32 R32 R32 R32
Connections Flare Flare Flare Flare
Liquid O.D. in 1/4 1/4 1/4 1/4
Suction O.D. in 3/8 3/8 1/2 1/2
Factory Charge Oz 25.8 25.8 38.8 45.9
Maximum Line Length Ft (m) 66 (20) 66 (20) 83 (25) 83 (25)
Line Length no additional charge
needed Ft (m)
25 (7) 25 (7) 25 (7) 25 (7)
Maximum Height Ft (m) 33 (10) 33 (10) 50 (15) 50 (15)