4. Line Set Size and Refrigerant Charge
NOTICE
The icemaker, line set, and remote condenser unit must contain the same type
of refrigerant. Mixing of refrigerants will result in improper operation and possible
damage to the refrigeration system.
Line Set Size and Refrigerant Charge
Hoshizaki
Icemaker
Hoshizaki
Remote
Condenser
Unit
Line Set
Up to 66' (20 m)
Line Set
Greater than 66' (20 m)
Maximum 100' (30.5 m)
Liquid
Line
Discharge
Line
Charge
Adjustment
Liquid
Line
Discharge
Line
Charge
Adjustment
(R-404A)
F-1501MRJZ(-C)(-SC) URC-14FZ 3/8"
OD
1/2" OD Not
Applicable
3/8"
OD
1/2" OD Add 0.4 oz.
for each foot
over 66' (40 g
for each meter
over 20 m).
Write new
total charge
on icemaker’s
rating label.
F-2001MRJZ/3(-C(-SC) URC-22FZ 3/8"
OD
5/8" OD Not
Applicable
3/8"
OD
5/8" OD