WARNING
• Repairs requiring the refrigeration circuit to be opened must be performed by
properly trained and EPA-certified service personnel.
• Always recover the refrigerant and store it in an approved container. Do not
discharge the refrigerant into the atmosphere.
• The gas R290 is not necessary recover; can be in a well ventilated area with no
source of ignition
• Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of
refrigerant to the system (if using an electronic leak detector), and then raise the
pressure using nitrogen gas (140 PSIG). Do not use R-134a a mixture with
pressurized air for leak testing.
NOTICE
• Do not leave the system open for longer than 15-min. when replacing or servicing
parts. The Polyol Ester (POE) oils used in R-134a and R-404A appliances can
absorb moisture quickly. Therefore it is important to prevent moisture from
entering the system when replacing or servicing parts.
• Always install a new drier every time the sealed refrigeration system is opened.
• Do not replace the drier until after all other repair or replacement has been made.
Install the new drier with the arrow on the drier in the direction of the refrigerant
flow.
• When brazing, protect the drier by using a wet cloth to prevent the drier from
overheating. Do not allow the drier to exceed 250°F (121°C).
A. Service for Refrigerant Lines
1. Refrigerant Recovery