Sealed encloSure cooling Air Conditioners
Spec-00728 G
EQUIPMENT PROTECTIONSUBJECT TO CHANGE WITHOUT NOTICEcooling1
SPEC-00728
G
763.422.2211
763.576.3200
cooling
SEALED ENCLO SURE COOLIN G
AIR CONDITIONERS
SPecTracool™ indoor/ouTdoor
G28
4000/6000 BTU/Hr.
1172/1758 Watt
G52
8000/12000 BTU/Hr.
2300/3500 Watt
G57
20000 BTU/Hr.
5861 Watt
G28
G52
G57
induSTrY STandardS
UL/cUL Listed; Type 12, 3R, 4; 4X optional; File No. SA6453
CE
GOST
IP 56 Internal Loop
IP 34 on External Loop
Telcordia GR-487 capable (Outdoor)
aPPlicaTion
Industrial automation
Telecommunications equipment
Waste water treatment systems
Package handling equipment
Security and defense systems
And more
FeaTureS
Energy-efficient rotary compressor on most models
R407c and R134a earth-friendly refrigerants
115, 230 and 400/460 VAC 3-phase power input on most models
UL Listed to save customers time and money with agency
approvals
Outdoor model operating temperature range from -40 F/-40 C to
131 F/55 C
Exterior and partially recessed mounting options
Attractive industrial design with minimal use of visible fasteners
Reliable mechanical thermostat on enclosure side of the unit;
indoor air conditioner models include digital display on ambient
side
Dual condenser-side air movers for performance redundancy on
G52 and G57 models
Galvanized sheet-metal cover for rugged factory and outdoor
environments
Easy-mount flanges for simple installation
Cut-out adapter options for enclosures with GENESIS™ and
T-Series air conditioners, enable users to easily transition to the
new unit
Dust-resistant condenser coil allows the unit to be run filterless
in most applications
Cleanable, reusable aluminum mesh filter protects coils for
maximum cooling performance
Mounting hardware, gaskets and user manual furnished with the
unit
Every unit functionally tested before shipping
Standard Indoor Air Conditioner models also include:
- Active condensate management with heater strip
- Power-off relay for door switch and other system
requirements
- Malfunction switch
Standard Outdoor Air Conditioner models also include:
- Telcordia GR-487 capable
- Corrosion-resistant components
- Malfunction switch
- Compressor heater
- Head pressure control
- Up to 2000 Watt (G28, G52) and 3000 Watt (G57) enclosure
heater
SPeciFicaTionS
Nominal cooling capacity:
G28 4000 & 6000 BTU/Hr. (1172 and 1758 W)
G52 8000 & 12000 BTU/Hr. (2344 and 3516 W)
G57 20000 BTU/Hr. (5861 W)
Outdoor model operating temperature range from -40 F/-40 C to
131 F/55 C
FiniSH
RAL 7035 light-gray, semi-textured powder-coat paint
Other colors and textures available
noTeS
Visit www.HoffmanOnline.com to download 2D and 3D CAD
drawings into the overall design of your electronic system.