Labelling
The equipment must bear a label indicating that it has been taken
out of service and emptied of its refrigerant. The label must be dated
and signed. For appliances containing flammable refrigerants, it
must be ensured that the equipment bears a label indicating that
it contains flammable refrigerants.
Recovery
When removing refrigerant from a system, whether for servicing or
decommissioning purposes, it is advisable to ensure that all
refrigerants are removed safely.
When transferring refrigerant to cylinders, ensure that only suitable
refrigerant recovery cylinders are used. Ensure that the correct
number of cylinders to contain the total system charge are available.
All cylinders to be used are designated for the refrigerant being
recovered and labelled for that refrigerant (i.e. special refrigerant
recovery cylinders). The cylinders must be equipped with a pressure
relief valve and the corresponding shut-off valves in good working
order. Empty recovery cylinders must be evacuated and, if possible,
cooled before recovery.
The recovery equipment must be in good working order,
accompanied by a set of instructions for the equipment available and
must be suitable for the recovery of all appropriate refrigerants,
including flammable refrigerants where appropriate. In addition,
a set of calibrated scales must be available and in good working
order. The hoses must be complete, fitted with watertight
connections and in good condition. Before using the recovery
machine, check that it is in good working order, that it has been
properly maintained and that all associated electrical components
are sealed to prevent ignition in the event of a refrigerant leak. If in
doubt, consult the manufacturer.
The recovered refrigerant must be returned to the refrigerant
supplier in the correct recovery cylinder and the corresponding
waste transfer note drawn up. Do not mix refrigerants in the
recovery units and especially not in the cylinders.
If compressors or compressor oils are to be removed, care must be
taken to ensure that they have been evacuated to an acceptable