3. System
Note
• Interface unit which the Ref. address 0, becomes main
interface unit.
• Connect AHU local controller (Part No. 7) to the main inter-
face unit.
Connect ONE remote controller (Part No. 2) to the interface •
unit.
Connect between the interface units with a remote controller•
(daisy chain).
Do NOT select STEP 0 for 3 minutes after compressor is •
ON. (Keep compressor ON for 3 minutes at least.)
When changing STEP, make it less than 5 steps in a single•
operation, and keep at least 5 minutes interval between the
changes.
Keep operation range shown at the following section 3.2.•
Do NOT send STEP 0 during defrost operation.•
Do NOT change operation mode frequently.•
No.
Part name
System
Interface unit
1
2
Remote controller
Outdoor unit
3
4
5
Target air temp. thermistor (TH1)
Coil temp. thermistor (TH2)
6
7
8
9
10
11
12
Air-Handling Unit(AHU) (Local supply)
Analog input/remote switch/modbus
Heat exchanger of AHU (Local supply)
Louver (Local supply)
Airfilter (Local supply)
Heat recovery (Local supply)
Fan (Local supply)
3.2. Indoor operation range
Mode
Number of outdoor unit
HEX inlet air temp. operation range
Cooling
Heating
1 or more
1
2 or more
15-32 ℃
0-28 ℃
5-28 ℃
6