DETERMINE THE NUMBER OF LINER SECTIONS
Saf-T Liner is available in 12", 18", 24", 36" and 48" fixed lengths and telescoping sections. NOTE: Two is the
maximum number of telescoping lengths which may be installed above the appliance tee. A telescoping section
between the appliance and clean out tee will allow for both radial and vertical adjustments during the installation.
To determine the length and number of liner sections required complete the following:Calculate the number of
fixed and/or telescoping lengths required to line the chimney and extend not more than 6" above the termination
of the masonry (Remember each fixed length’s measurement must be reduced by 2" to account for overlap of
each section)
-Determine the number of fixed or telescoping lengths between the appliance tee and the clean out tee (if
required).
DETERMINING THE AMOUNT OF SAF-T WRAP INSULATION
Saf-T Wrap is available in tee sections and 24" lengths, therefore two lengths will be required for each 4' section
of Saf-T Liner. Saf-T Wrap must cover the Saf-T Liner from the appliance tee or the top of the smoke chamber
area to within 8" but not closer than 3" of the top of the masonry chimney.
ASSEMBLY MATERIALS REQUIRED
The following tools and supplies are needed to complete the installation of the Saf-T Liner System:
•Hammer •1/8" or #30 high speed drill bit •Rope •Bag of mortar mix •Mortar pan •Screwdriver
•Eye protection •Cold chisel •Masonry drill bit •Electric or hand drill •Ladder and staging
•Tin Snips •Trowel •Duct tape •Pliers •Silcone caulking •Drop Cloth •Pop rivet gun
•Dust respirator (3M 9900, 3M8710 or equiv.)
PRE-ASSEMBLY OF SAF-T LINER PARTS
In order to reduce unnecessary trips up and down the ladder, the liner may be pre-assembled into sections 8-
10' in length. These can be safely carried up a ladder to the chimney. However, always check overhead for
antennaes, power lines, or other obstacles before erecting your ladder and installing liner. Preassemble the Saf-
T Liner on the ground and check the overall length. REMEMBER- the small, crimped end is always facing down
and the arrows marked on each liner section are to point up. Using the high speed drill bit, drill through the pilot
holes of one section into the crimped end of the next section. Pop rivet the liner into manageable lengths using
the four rivets supplied.
Non-Fireplace Chimney
In the case of a straight chimney liner job, the clean out tee should be riveted to the first liner section and the tee
cover attached to the tee. Place either a telescoping section or slip connector and a liner section between the
cleanout tee and the appliance tee to allow for expansion and contraction of the system.
Hearth/Fireplace Insert Stove
The appliance connector should be riveted to the first liner section with four opposing pop rivets.
ATTACHING LOWERING ROPE
The lowering rope should be attached to the first section of Saf-T Liner by any one of many methods including,
S hooks, duct tape or by riveting loops into place on the liner. Use any method that will provide a secure hold
on the liner and allow easy removal of the rope after installation.
When using telescoping sections, it will be necessary to attach an additional length of rope that will drop to the
base of the chimney flue. This rope will extend the telescoping sections as they are lowered into the chimney.