10/19 Model 9001EXP Page 2 of 6
RECOMMENDED TOOLS: Pipe joint sealant, screwdriver, pipe wrench, 14 AWG wire, ¾”
conduit and basic electricians’ tools for power connection.
LOCATION OF UNIT: The Model 9001EXP Alarm may be mounted directly to the upper stand
pipe of a safety shower or wall mounted next to a shower or eyewash. The alarm should be
clearly visible from several directions.
ELECTRICAL SUPPLY: 120 VAC 50/60 HZ, 20 Watts average power consumption. Suitable
for use in Class I, Division 2, Group B, C, D areas; Temperature rating T2C (230°C) with 60
Watt lamp /T2A (280
C) with 100 Watt lamp. Unit supplied with 8 Watt LED lamp. WARNING:
Power shall be supplied by a dedicated circuit through a 10 AMP maximum breaker or fuse and
should not supply any power to any other devices.
WATER SUPPLY: The flow switch requires a minimum of 2.4 GPM to activate. Mount flow
switch in supply line with flow in horizontal direction and switch stem extending vertically from
tee. Mount switch with at least 6” of straight pipe on both sides to minimize turbulence in switch.
TROUBLESHOOTING
PROBLEM
REPAIR CHECKLIST
1.
Alarm horn and light do not
operate.
1a.
Check incoming circuit for power and power
from flow switch.
b.
Check that the direction of water flow
corresponds to the arrow on the flow switch
body.
c.
Check that water flow is sufficient.
d.
Check all electrical connections for security,
including those in alarm base.
e.
Faulty flow switch. Replace entire switch
assembly.
f.
Faulty flasher module in alarm. Replace flasher
module.
2.
Horn sounds but light does not
flash.
2a.
Only replace lamp with Haws P/N 0003225505.
(See sheet 2 of installation drawing)
b.
Should replacement lamp also fail to operate,
replace flasher module.
3.
Lamp replacement.
3a.
Remove the guard from the light fixture, and
then unscrew the glass lens to replace the
lamp. Only replace lamp with Haws P/N
0003225505. (See sheet 2 of installation
drawing)
4.
Alarm stays on.
4a.
Check wiring connections.
b.
Disconnect flow switch wires and test for
continuity.