14 31-5000493 Rev. 4
Installation Instructions
Final Check
Start Up Checklist
Ƒ Refrigerant charge is verified and system has been
leak tested
Ƒ Line sets have been insulated
ƑElectrical connections are secure
Ƒ Electrical ground has been checked and verified
Ƒ Electrical wiring terminals match at indoor and outdoor
unit
Ƒ Wire between outdoor and indoor must be 14/4 non-
shielded stranded copper cable
Ƒ Outdoor to indoor wires 1, 3, and Ground are free of
splices
Ƒ Condensate drain has correct pitch and has been leak
tested insulated to avoid condensate.
Ƒ Verify 100% pump reservoir drains to avoid risks of
legionnaires.
Ƒ Check reservoir for any contaminates from installation
that could promote bacteria growth
Ƒ Indoor and outdoor units are compatible
Ƒ Indoor and outdoor units are firmly mounted
Ƒ Power source voltage is within +/- 10% tolerances
Ƒ The indoor and outdoor sections are quiet and free of
vibration
Ƒ All functions of the controller have been verified
Ƒ Operation in cooling or heating modes is normal
(see sequence of operation in service manual)
Ƒ Operation of the system has been explained to the
owner
Ƒ Indoor unit capacity check has been completed
Explaining Operation to the End User
Ƒ Using the User Manual, explain to the user how to use the air conditioner/heat pump:
• the wired controller
• adding/removing the air filters
• placing or removing the wired controller from the wired control holder
• cleaning methods
• precautions for operation, etc
Ƒ Review precautions for operation.
Ƒ Recommend that the user read the Operating Instructions carefully.
ƑLeave this manual with the end user - that way future service techs can verify these steps were completed if they
have problems
Service Tech:________________________________ Phone number:___________________ Date:___________
Service Tech:________________________________ Phone number:___________________ Date:___________
Service Tech:________________________________ Phone number:___________________ Date:___________
Service Tech:________________________________ Phone number:___________________ Date:___________