Installation Instructions: Introduction and Overview
Condensate Handling
The Cassette unit has a built in condensate pump and
water level safety switch. There is no option for gravity
drain. The condensate pump is rated to lift water up to
47 3/16” from the point of discharge on the cassette
assembly. Recommended pump flow rate is 0.106 gpm
to 0.159 gpm.
The cassette unit comes with a grey connection
hose with clamp. This hose is connected to the
cassette assembly discharge hose port. The other
end of the hose is sized to accept 3/4 “ PVC piping.
Recommended condensate piping configurations are
shown here:
Electrical Power
Follow all local codes and regulations when installing
electrical wiring.
Route required electrical power to area where the
Cassette unit is to be located. Maintain at least a 10 foot
separation between TV, Radio or any communication
wiring and the power to the indoor unit.
14/4 AWG SOOW Non- Shielded Stranded Copper
Cable should be used to make the electrical connection
and communication link between indoor and outdoor
units.
16/2 AWG Shielded SOOW Cable should be used for
high speed communication on H1 and H2 terminals.
Note: In applications with multiple indoor units, only
connect one indoor unit to the outdoor unit with the
high speed communication cable. It is recommended
to connect the indoor unit that is closest to the outdoor
unit.
The wiring is connected at the indoor unit electrical
terminal blocks screws 1, 2, 3 and ground. There should
be no splices in the wires between the indoor and
outdoor units as these serve as communication signal
wires and electrical power connections. Any accessory
added to shut off power to the indoor section should
break the Number 2 terminal only.
Air Delivery Clearances
Make certain to maintain proper clearances around the
cassette as specified in the installation instructions.
Standard clearances for cassette air handlers require
5 feet of clearance in each direction. There should be
8 feet of clearance from the face of the cassette grille
to the floor. Inadequate clearances can cause system
freezing and temperature control problems.
Fresh Air Intake Option
The cassette has a marked area to cut out if outside air
is desired. The piping connection should be made with
a 4 inch diameter pipe. Outside air should be pre-filtered
prior to entry into the cassette.
8 1/4 (210)
Ø 4 (100)
Service and Maintenance Clearances
Make sure there are adequate clearances for future
maintenance and service. Allow enough room to access
the condensate pump assembly and the electrical
control box.
12 in. below
3-5 ft.
11 in.
8.6 in.
8.6 in.
19.6 in.