Hager VR10129005 handleiding

64 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 9 van 64
Floor installation systems
FAQs
Answer 2: How is the cable volume calculated?
The cable volume is required to define the correct duct size. However, as, in practice, cables can nev-
er lay next to each other in a perfectly parallel and space-saving manner, the formula (d)² or the diame-
ter squared is used. The trunking should only be 50% full, to leave space for possible refitting later on.
This means that the cables can also be pulled through the trunking more easily.
In addition, it should be noted that, in this calculation, no floor tanks or outlets which might interrupt
the cable path are taken into account. In practice, power and data cables are routed separately in the
trunking. Separating webs divide the trunking up into multiple compartments. If this applies, then the
space requirements must be calculated for each compartment individually.
With stronger current loads of the cables, cable heating should be taken into account. In addition, all
the relevant regulations, such as DIN VDE 0100, must also be taken into account.
9

Bekijk gratis de handleiding van Hager VR10129005, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkHager
ModelVR10129005
CategorieNiet gecategoriseerd
TaalNederlands
Grootte13434 MB

Caratteristiche Prodotto

Kleur van het productZwart
CertificeringEN50085-2-2
DuurzaamheidscertificatenRoHS
Aantal1