Floor installation systems
Answer 2: How is the cable volume calculated?
The cable volume is required to define the correct duct size. However, as, in practice, cables
can never lay next to each other in a perfectly parallel and space-saving manner, the formu-
la (d)² or the diameter squared is used. The ducts should only be 50% full, to leave space for
possible refitting later on. This means that the cables can also be pulled through the duct more
easily.
In addition, it should be noted that, in this calculation, no floor tanks or outlets which might inter-
rupt the cable path are taken into account.
In practice, power and data cables are routed separately in the duct. Separating webs divided
the duct up into multiple compartments. If this applies, then the space requirements must be cal-
culated for each compartment individually.
With stronger current loads of the cables, cable heating should be taken into account. In addi-
tion, all the relevant regulations, such as DIN VDE 0100, must also be taken into account.
Bekijk gratis de handleiding van Hager UKB190480, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
| Merk | Hager |
| Model | UKB190480 |
| Categorie | Niet gecategoriseerd |
| Taal | Nederlands |
| Grootte | 11902 MB |
Caratteristiche Prodotto
| Kleur van het product | Zink |
| Diepte | 59 mm |
| Certificering | EN50085-2-2 |
| Materiaal | Staal |
| Duurzaamheidscertificaten | RoHS |