6LE008221A
Floor installation systems
Basic manual
Page 28/61
Floor installation systems
Hot floor screed:
Screed-flush duct systems and boxes may not come into direct contact with the hot screed
mass. With film lining, there must be an approx. 10 cm-thick layer of cement screed, for
example, by the components for heat insulation. With metal lining and floor troughs, wa-
terproofed corrugated card, for example, can be used for insulation. Screed-covered ducts
must be protected against the hot screed mass with 2 - 3 layers of waterproofed corrugated
card.
P
Avoid cavities! Hager is not liable for any damaged cause by improper installation on the
duct system or the floor box in conjunction with hot screed!
Expansion pressure of the screed plate:
According to the size of the screed plate and the composition of the screen, it is possible that
the boxes may press against the electraplan.BK duct whilst the screed is hardening. For this,
Hager can offer a matching self-adhesive foam rubber strip (BKZM203), which is fitted in the up-
per profile area, in order to reduce the expansion pressure of the screed plate on the duct. The
use of the foam rubber strip must be agreed with the screed layer.