Determining the cable volume
Bend radii
Use the following table for the correct selection of the trunking size. In addition, these factors
from the current DIN/VDE standards must be observed:
Usable cross-section of the trunking
Filling factor
Heating up of the routed cables
Separation of heavy and weak current
Bend radii
Art. number Art. designation Width
[mm]
Height
min
[mm]
Height
max.
[mm]
Trunking cross-
section
[cm²]
[1]
Max. cable as-
signment Ø 11
mm Filling lev-
el 0.5
[1]
AKU1500401 On-floor trunking base 150 40 X 60 24
BKF400105 On-floor trunking, screed-
flush with the film
416 105 150 540 223
BKW200060 On-floor trunking, screed-
flush with the trough
216 60 100 88 36
BKFD150065 On-floor trunking, screed-
flush with the film/sealing
option
170 65 110 121 50
BKWD200090 On-floor trunking, screed-
flush with the trough/sealing
option
220 90 130 143 59
BKBD30080 Screed-flush floor trunking
with brush
300 80 X 240 70
BKGD30060 Screed-flush floor trunking,
closed
300 60 X 154 61
UK340483 Underfloor trunking, 3-com-
partment, screed-covered
340 48 X 163 65
Table 1: Trunking size/trunking cross-section/number of cables
Note!
Further details on Table 1 can be found in the Appendix.
6.1 Bend radii
Bend radii
Bend radii are dealt with in the standard VDE 0298 (Part 3) and must be complied with when routing
cables in floor installation systems.
[1]
Values are rounded
[1]
Internal levelling
33

Bekijk gratis de handleiding van Hager AKBI2000701, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkHager
ModelAKBI2000701
CategorieNiet gecategoriseerd
TaalNederlands
Grootte13434 MB

Caratteristiche Prodotto

Kleur van het productZink
Breedte200 mm
Diepte800 mm
Hoogte70 mm
MateriaalStaal