Floor installation systems
FAQs
Answer 2: How is the cable volume calculated?
The cable volume is required to define the correct duct size. However, as, in practice, cables can nev-
er lay next to each other in a perfectly parallel and space-saving manner, the formula (d)² or the diame-
ter squared is used. The trunking should only be 50% full, to leave space for possible refitting later on.
This means that the cables can also be pulled through the trunking more easily.
In addition, it should be noted that, in this calculation, no floor tanks or outlets which might interrupt
the cable path are taken into account. In practice, power and data cables are routed separately in the
trunking. Separating webs divide the trunking up into multiple compartments. If this applies, then the
space requirements must be calculated for each compartment individually.
With stronger current loads of the cables, cable heating should be taken into account. In addition, all
the relevant regulations, such as DIN VDE 0100, must also be taken into account.