associated shut-off valves in good working order. 
Empty recovery cylinders are evacuated and, if 
possible, cooled before recovery occurs.
The recovery equipment shall be in good working 
order with a set of instructions concerning the 
equipment that is at hand and shall be suitable 
for the recovery of all appropriate refrigerants 
including, when applicable, flammable 
refrigerants. In addition, a set of calibrated 
weighing scales shall be available and in good 
working order. Hoses shall be complete with leak-
free disconnect couplings and in good condition. 
Before using the recovery machine, check that it 
is in satisfactory working order, has been properly 
maintained and that any associated electrical 
components are sealed to prevent ignition 
in the event of a refrigerant release. Consult 
manufacturer if in doubt.
The recovered refrigerant shall be returned to 
the refrigerant supplier in the correct recovery 
cylinder, and the relevant waste transfer note 
arranged. Do not mix refrigerants in recovery 
units and especially not in cylinders.
If compressors or compressor oils are to be 
removed, ensure that they have been evacuated 
to an acceptable level to make certain that 
flammable refrigerant does not remain within 
the lubricant. The evacuation process shall be 
carried out prior to returning the compressor 
to the suppliers. Only electric heating to the 
compressor body shall be employed to accelerate 
this process. When oil is drained from a system, it 
shall be carried out safely.
2  Maintenance instruction