6.5.3 USB connection
1> Loosen the waterproof cover of the USB interface and remove it.
3> As shown in Fig 6.24, make sure that the ▲ is facing frontwards as the inverter
has been wall-mounted, insert the monitoring module into the USB interface,
and tighten the lock.
Note:
The WIT-XHU series inverter is equipped with a USB interface as standard, which
can be connected to a USB to WiLAN-X2 monitoring module for remote monitoring.
In addition, you can also quickly upgrade the inverter software through the U disk.
Steps to install the monitoring module:
2> As shown in Fig 6.24, insert the WiLAN-X2 module into the USB interface, and
the LED indicator of the WiLAN-X2 module will be on.
If a USB to WiLAN-X2 module is installed, please take the module and the data
cable away, and tighten the waterproof cover when the operator leaves to prevent
water from entering the interface.
NOTE:
The external communication terminal of the WIT 29.9-50K-XHU Inverter is a 4-pin
connector. The matching terminal is in the accessory kit. The connection
procedure is as follows:
1. Connect the communication cable to the corresponding terminal as required.
Fig 6.22 COM2 communication terminal
2. The COM2 communication terminal contains two dry contacts (voltage free). PIN
1 and 2 are for emergency stop signal; PIN 3 and 4 are for DG start-up signal.
Inverter Internal Relay
Diesel generator
startup signal
COM2
(pin3)
COM2
(pin4)
Fig 6.23
Note: Maximum dry contact input: 24VDC 1A.
Fig.6.24 USB Connection
1 2 3
48
47
COM2 terminal(user side)
Loosen
Tighten