Warning
Description
Suggestion
Warning 209
DC input voltage
exceeds the upper
threshold
2. If the DC voltage is within the
specified range and the error message
persists, contact Growatt support.
1. Turn off the DC switch immediately
and check the DC voltage.
PV Reversed
PV string is reversely
connected
1. Check the polarity of the PV terminals.
2. If the error message persists, contact
Growatt support.
Warning 219
PID function
abnormal
1. Restart the inverter.
2. If the error message persists, contact
Growatt support.
Warning 220
PV string
disconnected
2. If the error message persists, contact
Growatt support.
1. Check if the PV string is properly
connected.
Warning 221
PV string current
unbalanced
1. Check if the PV panels of the
corresponding string are normal.
2. If the error message persists, contact
Growatt support.
Warning 300
No utility grid
connected or utility
grid power failure
1. Check if the grid is down.
2. If the error message persists, contact
Growatt support.
Warning 301
Grid voltage is
beyond the
permissible range
1. Check if the grid voltage is within the
specified range.
2. If the error message persists, contact
Growatt support.
Warning 302
Grid frequency is
beyond the
permissible range
1. Check if the grid frequency is within
the specified range.
2. If the error message persists, contact
Growatt support.
Warning 303
Overload
1. Please reduce the load connected to
the EPS output terminal.
2. If the error message persists, contact
Growatt support.
Warning 308
Meter disconnected
1. Check if the meter is properly
connected.
2. If the error message persists, contact
Growatt support.
110
109
Warning
Description
Suggestion
Warning 309
Meter is reversely
connected
1. Check if the L line and the N line of the
meter are reversely connected.
2. If the error message persists, contact
Growatt support.
Warning 310
The voltage
difference between
the N line and the PE
cable is abnormal
1. Check if the PE cable is reliably
connected after shutdown.
2. If the error message persists, contact
Growatt support.
Warning 311
Phase sequence
error
No operation is required. The PCS will
automatically adjust the phase
sequence.
Warning 400
Fan failure
2. If the error message persists, contact
Growatt support.
1. Check if the fan is properly connected
after shutdown.
Warning 401
Meter abnormal
1. Check if the meter is turned on.
2. If the meter is correctly connected to
the inverter.
Warning 402
Communication
between the
optimizer and the
inverter is abnormal
2. If the optimizer is correctly
connected to the inverter.
1. Check if the optimizer is turned on.
Warning 407
Over-temperature
2. If the error message persists, contact
Growatt support.
1. Restart the inverter.
Warning 408
NTC temperature
sensor is broken
2. If the error message persists, contact
Growatt support.
1. Restart the inverter.
Warning 411
Sync signal
abnormal
2. If the error message persists, contact
Growatt support.
1. Check if the sync cable is abnormal.
Warning 412
Startup
requirements of grid
connection are not
met
1. Check if the grid voltage is within the
specified range and check if the grid-
connection startup voltage
configuration is correct.
2. Check if the PV voltage is within the
specified range.
3. Restart the inverter. If the error
message persists, contact Growatt
support.