Error message
Inverter fault code
LCD Display
Suggested measure
Error 300
AC V Outrange (1)
1. Check the grid voltage.
2. If the error message still exists despite the
grid voltage being within the permissible
range, please contact Growatt support.
Error 300
AC V Outrange (2)
1. Check the grid voltage.
2. If the error message still exists despite the
grid voltage being within the permissible
range, please contact Growatt support.
Error 300
AC V Outrange (3)
1. Check the grid voltage.
2. If the error message still exists despite the
grid voltage being within the permissible
range, please contact Growatt support.
Error 304
AC F Outrange
1. Restart the inverter.
2. If the error message still exists, please
contact Growatt support.
Error 302
No AC Connection
1. Check the grid voltage.
2. If the error message still exists despite the
grid voltage being within the permissible
range, please contact Growatt support.
Error 604
EPS Volt Low
1. Restart the inverter.
2. If the error message still exists, please
contact Growatt support.
Error 607
EPS Over Load
1. Restart the inverter.
2. If the error message still exists, please
contact Growatt support.
Error 505
Battery reversed
1. Check battery terminals.
2. If the error message still exists, please
contact Growatt support.
Error 506
Battery Open
1. Check battery terminals.
2. If the error message still exists, please
contact Growatt support.
Error 502
Bat Voltage Low
1. Check battery voltage.
2. If the error message still exists, please
contact Growatt support.
Error 503
Bat Voltage High
1. Check battery voltage.
2. If the error message still exists, please
contact Growatt support.
Error 500
BMS COM Fault
1. Check the battery communication port.
2. If the error message still exists, please
contact Growatt support.
Error 402
Output High DCI
1. Restart the inverter.
2. If the error message still exists, please
contact Growatt support.
Error message
Inverter fault code
LCD Display
Suggested measure
Error 203
PV Isolation Low
1. Check if the PV panel enclosure is properly
grounded.
2. If the error message persists, please
contact Growatt support.
Error 202
PV Voltage High
1. Disconnect the DC switch immediately
and check the voltage.
2. If the DC input voltage is within the
permissible range and the error message
persists, please contact Growatt support.
Error 600
OP Short Fault
1. Restart the inverter.
2. If the error message still exists, please
contact Growatt support.
PV1 short
Pv1 short
2. If the error message persists, please
contact Growatt support.
1. After shutdown, check is the PV panel is
normal.
PV2 short
Pv2 short
2. If the error message persists, please
contact Growatt support.
1. After shutdown, check is the PV panel is
normal.
CT LN Reversed
CT LN Reversed
1. Check if the CT is properly connected.
2. If the error message still exists, please
contact Growatt support.
Error 507
Over Load
1. Check if the load power is greater than
the lithium battery rated power.
2. If the error message still exists, please
contact Growatt support.