9 Fault removal
Growatt products have gone through strict tests and inspections before delivery. As with
all electrical devices, there are residual risks despite careful construction. Should you
encounter any problems, you can visit www.ginverter.com to check the Q&A section or
call our customer service line. We require the following information in order to provide
you with the necessary assistance:
Ø Inverter serial number
Ø Inverter model
Ø Fault information on the LCD screen
Ø The manufacturer and model of the battery
Ø When did the fault occur?
Ø Brief introduction of the problem
Ø The capacity and wiring mode of the battery
Ø Purchase time of the battery and the use frequency
Ø Can you reproduce the problem?
Ø The grid voltage and frequency
Ø The battery voltage
Ø Has the problem occurred before?
Warning Message
Error message
Description
Suggestion
Warning401
Meter Communication fault
Check the wire connection between
the meter and the inverter.
Warning506
Battery temperature out of
specified range for charge or
discharge
Check if the ambient temperature of
the battery is beyond the specified
range.
AC V Outrange
Grid voltage fault.
Please refer to the local grid
standard for more details about
the grid voltage.
2. Check the grid connection.
1. Check if the grid voltage is beyond
the specified range.
AC F Outrange
Grid frequency fault.
Please refer to the local grid
standard for more details about
the grid frequency.
2. Restart the inverter.
3. Please contact Growatt support if
the problem persists after restart.
1. Check if the grid frequency is
beyond the specified range.
BMS COM Fault
Communication fault
1. Check if the lithium battery has
been turned on.
2. Check the connection between
the lithium battery and the inverter.
Battery reversed
Battery terminals reversed
Check the polarity of the battery
terminals.
9.1 System fault information list and troubleshooting suggestions
Warning Message
Error message
Description
Suggestion
Battery Open
Battery terminal open
(only for lithium battery)
1. Check the battery connection.
2. Check if the switches between the
battery and the inverter have been
turned on.
Over load
EPS output overload warning.
If this warning occurred three
times, the off-grid function
will be locked for one hour.
Please reduce the load connected to
the EPS output port.
No AC
Connection
No Utility
3. Check if the switches have been
turned on.
1. Check if the grid goes down.
2. Check the grid connection.
Output High DCI
High DC component in the
output power.
Please refer to the local grid
standard for disconnection
time when the output DC
current is too high.
2. Please contact Growatt support if
the problem persists after restart.
1. Restart the inverter.
Bat Voltage High
Battery Voltage higher than
560V
1. Check if the battery voltage is
within the specified range.
2. Check the battery connection. If
the actual battery voltage is higher
than 560V, please disconnect the
battery and check the inverter.
Bat Voltage Low
Battery Voltage lower than
100 V
2. Check the connection between the
battery and the inverter.
1. Check if the battery voltage is
within the specified range.
BMS
Warning:XXX
BMS report warning
2. Please contact Growatt support if
the problem persists after restart.
1.Check the warning information
referring to the lithium battery user
manual.
BMS error:XXX
BMS report error
2. Please contact Growatt support if
the problem persists after restart.
1.Check the warning information
referring to the lithium battery user
manual.
EPS Volt Low
EPS output voltage low
1. Check the power of the load
connected to the EPS output port. If
overload occurs, please reduce the
load.
2. Restart the inverter.
7271