13
Dry Contact Signal
There is one dry contact(3A/250VAC) available on the rear panel. It could be used to deliver signal to external
device when battery voltage reaches warning level. (Note: Mains and diesel generators cannot be connected
to the mains input of this machine at the same time, only one of them can be connected).
Unit Status
Condition
Dry contact port:
NC & C
NO & C
Power Off
Unit is off and no output is powered.
Close
Open
Power On
Output is off and no output is powered
Close
Open
Battery not in “LI”
mode
Battery voltage <
Low DC Cut-off Voltage +2Vdc
Open
Close
Battery Voltage reaches setting in 13
Close
Open
Battery in “LI” mode
Battery SOC <
Low DC Cut-off Soc +5%
Open
Close
Battery Voltage reaches setting in 13
Close
Open
Maintenance
Heat dissipation performance is very important when SPF inverter work under the environment of high
temperature,better heat dissipation can reduce the possibility of SPF inverter failure.
GROWATT SPF series inverters are with IP20 enclosure,which use fan cooling method.To make sure the system runs
properly,please notice the environment temperature should be in -20~50℃ and try installing the system in dry
environment. For maintenance, to make sure the inverter can dissipate the heat properly, please try clean the dust
from air inlet and outlet regularly.
CAUTION- During maintenance and repair, the circuit breaker needs to be disconnected.