Growatt SPF3000-6000T-HVM-G2 handleiding
Handleiding
Je bekijkt pagina 12 van 48

10
connection. To reduce risk of injury, please use the proper recommended cable size as below.
Suggested cable requirement for AC wires
Model
Gauge
Torque Value
SPF 3000T HVM-G2
1 * 10 AWG
1.2-1.6 Nm
SPF 6000T HVM-G2
1 * 8 AWG
1.2-1.6 Nm
Please follow below steps to implement AC input/output connection:
1.
Before making AC input/output connection, be sure to open DC protector or disconnector first.
2.
Cut the insulation sleeves of the six conductors by 10mm..
3.
Insert AC input wires according to polarities indicated on terminal block and tighten the terminal screws. Be
sure to connect PE protective conductor first.
→Ground (yellow-green)
L
→
LINE (brown or black)
N
→
Neutral (blue)
WARNING:
Be sure that AC power source is disconnected before attempting to hardwire it to the unit.
4.
Then, insert AC output wires according to polarities indicated on terminal block and tighten terminal screws. Be
sure to connect PE protective conductor first.
→Ground (yellow-green)
L→LINE (brown or black)
N
→
Neutral (blue)
5.
Make sure the wires are securely connected.
6.
Make sure the metal shell of the inverter and the AC output are grounded.
R-type terminal:
→Ground (yellow-green)