Growatt SPF 4-12KT HVM handleiding
Handleiding
Je bekijkt pagina 10 van 32

8
AC Input/Output Connection
CAUTION!!
Before connecting to AC input power source, please install a separate AC breaker between inverter and AC
input power source. This will ensure the inverter can be securely disconnected during maintenance and fully
protected from over current of AC input. The recommended spec of AC breaker is 40A for 4KW~6KW, 80A
for 8KW~12KW.
There are two terminal blocks with “IN” and “OUT” markings. Please do NOT mis-connect input and output
connectors.
WARNING! !
All wiring must be performed by a qualified personnel.
It‟s very important for system safety and efficient operation to use appropriate cable for AC input connection.
To reduce risk of injury, please use the proper recommended cable size as below.
Suggested cable requirement for AC wires
Model
Gauge
Torque Value
4KW/5KW
10 AWG
1.4~ 1.6 Nm
6KW/8KW
8 AWG
1.4~ 1.6 Nm
10KW/12KW
6 AWG
1.6~ 1.8 Nm
AC Wiring
4KW/5KW/6KW, 230V single phase
Input: Hot line + Neutral + Ground
Output: Hot line + Neutral + Ground
8KW/10KW/12KW, 230V single phase
Input: Hot line + Neutral + Ground
Output: Hot line + Neutral + Ground
Please follow below steps to implement AC input/output connection:
1.
Before making AC input/output connection, be sure to open DC protector or disconnector first.
2.
Remove insulation sleeve 10mm for six conductors. And shorten phase L and neutral conductor N 3 mm.
3.
Insert AC input wires according to polarities indicated on terminal block and tighten the terminal
screws. Be sure to connect PE protective conductor first.
Bekijk gratis de handleiding van Growatt SPF 4-12KT HVM, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
| Merk | Growatt |
| Model | SPF 4-12KT HVM |
| Categorie | Niet gecategoriseerd |
| Taal | Nederlands |
| Grootte | 5108 MB |







