Danger
Warning
16
15
6 Inverter wiring
6.1 Security
There may be a high voltage in the conductive part of the inverter,
which may cause electric shock.Therefore, when installing the
inverter,make sure that the AC and DC sides of the inverter are
powered off.
Static electricity may damage the electronic components of the
inverter.Anti-static measures should be taken during the
replacement or installation of the inverter.
Moisture and dust penetration can damage the inverter
Ø Make sure that the waterproof cable gland is firmly tightened.
Ø If the cable connector is not installed correctly, the inverter
may be damaged due to the penetration of moisture and dust. All
warranty claims are void
Note
6.2 AC side wiring
Before making electrical connections, please make sure that
disconnect the battery and disconnect the AC side MCB,
otherwise the high voltage of the inverter may cause death.
Ø Each inverter must be installed with an AC circuit breaker
independently, and it is forbidden to share multiple inverters.
Ø It is forbidden to use single-core wire at the output terminal of
the inverter.
Ø It is forbidden to use aluminum wires as output cables.
Ø Please ensure that the output cable is well connected
before turning on the inverter.Ignoring the above warning
may damage the machine or cause other losses.In this case,
the company reserves the right not to carry out the warranty
and bear any responsibility and related expenses.
Moisture and dust penetration can damage the inverter.
Ø Make sure the cable connector is securely tightened.
Ø If the cable connector is not installed correctly, the inverter
may be damaged by moisture and dust. All warranty claims are
invalid.
Danger
Warning
Note
You must install a separate three phase circuit-breaker or other load disconnection unit
for each inverter in order to ensure that the inverter can be safely disconnected under
load.
We suggest you choice the AC breaker rating current in this table:
Inverter model
Switch specification
MOD 3000TL3-XA
10A(230/400V)
MOD 4000TL3-XA
10A(230/400V)
MOD 5000TL3-XA
15A(230/400V)
MOD 6000TL3-XA
15A(230/400V)
MOD 7000TL3-XA
15A(230/400V)
MOD 8000TL3-XA
20A(230/400V)
MOD 9000TL3-XA
20A(230/400V)
MOD 10KTL3-XA
20A(230/400V)
AC connection steps :
1.Pass the 5 wires (A,B,C,N and PE wires) through the AC shield,crimp the O/U terminal
and connect to the screw terminals on the AC connector.
a
b
c
Fig 6.1 AC output wiring diagram
Residual current protection device (RCMU)
Because the inverter itself has a high-precision residual current detection device,it is
not recommended to install a leakage protection switch in the system.If for some
special reason,it must be installed between the inverter output and the grid.Please
install a type A leakage protection switch no less than 300mA.When multiple
leakage protection switches are installed in the system,it is forbidden to share the
neutral line,otherwise the leakage protection function may be triggered by mistake
and cause the switch to trip.