13.3 System error
Error code
Description
Suggest
Error 200
DC arc abnormal
1.Check the panel terminal wiring after shutdown;
2.Restart the inverter;
3.If the fault message still exists,contact the
manufacturer.
Error 201
Leakage current is
too high
1.Restart the machine;
2.If the fault information still exists,contact the
manufacturer.
Error 202
Panel voltage is too
high
1.Disconnect the DC switch immediately and
confirm the voltage;
2.After the normal voltage is restored,if the fault
message still exists,contact the manufacturer.
Error 203
Low panel
insulation
resistance
1.After shutting down, check whether the panel
shell is reliably grounded;
2.If the fault message still exists,contact the
manufacturer.
Error 300
The mains voltage
is abnormal
1.Check the grid voltage;
2.If the grid voltage has recovered to the allowable
range and the fault information still exists,contact
the manufacturer.
Error 301
AC wiring error
1.Please check the mains terminal;
2.If the fault message still exists,contact the
manufacturer.
Error 302
No mains
connection
1.Check the AC side line connection after
shutdown;
2.If the fault message still exists,contact the
manufacturer.
Error 303
Zero ground
detection anomaly
1.Check the ground wire after shutting down to
ensure that the ground wire is connected reliably;
2.If the fault message still exists,contact the
manufacturer.
Error 304
Abnormal mains
frequency
1.Detect grid frequency and restart;
2.If the fault message still exists,contact the
manufacturer.
Error 305
Output overload
protection
1.Check output load, reduce load power;
2.If the fault information still exists,contact the
manufacturer
Error 306
Reverse
connection of
current transformer
1.Check the connection direction of the current
transformer after shutdown;
2.If the fault information still exists,contact the
manufacturer.
Error 307
Communication
failure of current
transformer
1.Please check the communication line;
2.If the fault information still exists,contact the
manufacturer.
Error 308
Pairing timeout
1.The pairing of the machine and the current
transformer is overtime, re-pair;
2.If the fault information still exists,contact the
manufacturer;
Error code
Description
Suggest
Error 400
Abnormal DC
component offset
1.Restart the machine;
2.If the fault information still exists,contact the
manufacturer.
Error 401
The output
voltage DC
component is too
high
1.Restart the machine;
2.If the fault information still exists,contact the
manufacturer.
Error 402
The output
current DC
component is too
high
1.Restart the machine;
2.If the fault information still exists,contact the
manufacturer.
Error 403
Unbalanced
output current
1.Check whether the output current is unbalanced
after shutdown;
2.If the fault message still exists, contact the
manufacturer.
Error 404
Bus voltage
sampling is
abnormal
1 Restart the machine
2: If the fault information still exists, contact the
manufacturer
Error 405
Relay abnormal
1.Restart the machine;
2.If the fault information still exists, contact the
manufacturer.
Error 406
Initialization
mode exception
1.Reset mode;
2.If the fault message still exists,contact the
manufacturer.
Error 407
Automatic
detection failed
1.Restart the machine;
2.If the fault information still exists,contact the
manufacturer.
Error 408
Temperature is too
high
1.Check the temperature after shutdown,restart the
inverter after normal;
2.If the fault message still exists,contact the
manufacturer.
Error 409
Abnormal bus
voltage
1.Restart the machine;
2.If the fault information still exists, contact the
manufacturer.
Error 410
Inconsistent
insulation
resistance
sampling
1.Restart the machine;
2.If the fault information still exists,contact the
manufacturer.
Error 411
Internal
communication
abnormal
1.Check the wiring of the communication version
after shutdown;
2.If the fault message still exists, contact the
manufacturer.
Error 412
Temperature
sensor connection
abnormal
1.Check whether the temperature sampling module
is properly connected after shutdown;
2.If the fault message still exists,contact the
manufacturer.