Preparation before wiring:
Connect the protective ground wire (PE)
Connect the inverter to the grounding bar through the protective earth (PE) to achieve
grounding protection.
Ø Good grounding is good for resisting surge voltage impact
and improving EMI performance. Therefore,you need to ground
the wire before connecting the AC,DC,and communication
cables.
Ø For a single-machine system,only the PE cable needs to be
grounded;For a multi-machine system,the PE cables of all
inverters need to be connected to the same grounding copper
bar to ensure equipotential connection.
Ø Disconnect the inverter DC switch,AC side circuit breaker or switch.
Ø Measure the voltage and frequency of the public grid (voltage:AC 230V;
frequency:50Hz)
Ø
The recommended specifications of the AC output switch are as follows:
Inverter model
Switch specification
MID 15-25KTL3-XL2
100A/230V
MID 30-33KTL3-X2
80A/230V
MID 36KTL3-X2
100A/230V
MID 40KTL3-X2
100A/230V
MID 50KTL3-X2
100A/230V
17
Fig 6.1 Grounding diagram
AC connection steps(just for Vietnam models):
1.Pass the 5 wires (L1,L2,L3,N and PE wires) through the AC shield,connect them to the
power grid, and then crimp the O/U terminal.
2. Lock the AC cable to the corresponding AC terminal.
3.Lock the protective cover on the inverter frame, and finally tighten the protective cover
hole.
Fig 6.2
Fig 6.3
Fig 6.4
10-12mm
Noted:Waterproof must be blocked with fireproof mud to prevent water.