7 Debugging
1.Close the DC switch on the inverter.As long as the input DC voltage is greater
than 140V,the inverter display will show the following information:No mains
connection error,the inverter LED will turn red.
If other information is displayed,please refer to Chapter 13.If you encounter any
problems during the debugging process and cannot solve it,please contact
customer service.
2.Close the circuit breaker or switch between the inverter and the grid, the
inverter will start a countdown to the self-check,and after the self-check is
normal,it will be connected to the grid.
3.In normal operation,the leaves of the inverter indicator window will turn green.
4.Finish debugging.
29
30
6.8.4 Earth Fault Alarm
The inverter complies with AS/NZS 5033.When the Earth fault occurs, the Red LED
will light up.The buzzer in the inverter will keep ringing unless the fault condition is
cleared(This function is only avilable for Australia and New Zealand).
Working Mode 8
8.1 Normal mode
In this mode, the inverter works normally.
Ø When the DC voltage is greater than 250V, the energy is sufficient, and the grid
voltage frequency meets the grid-connected requirements, the inverter will
convert the energy of the solar panels into AC power and export to the grid, and
the green LED will light up.
Ø When the DC voltage is lower than 180V, the inverter will automatically
disconnect from the grid and exit the normal operation mode. When the input
voltage reaches the requirement again and the grid voltage and frequency return
to normal, the inverter will automatically connect to the grid.
8.2 Failure mode
The inverter controls the chip monitors and adjusts the state of the system in real time.
When the inverter monitors any unexpected conditions,such as system failure and
inverter failure,the display will show the fault information.In the failure mode,the
inverter will indicate The leaves of the window will turn red and the inverter output will
be disconnected from the grid.
When the sunlight is weak or there is no sunlight,the inverter will automatically stop
running.When in shutdown mode,the inverter basically does not consume energy from
the grid or solar panels,and at the same time,the inverter's display screen and LED
lights will be turned off.
8.3 Shutdown mode
If there is PV isolation low alarm, there might be some fault for the inverter case
ground protection,please do not touch the inverter case.