7 Commissioning
7.1 Checking before powering on the system
No.
Checking items
Criteria
1
Installation of the
inverter
The inverter is securely installed
2
Cable layout
The communication cables and the power
cables are separated
3
Grounding
The grounding cable is correctly and
properly connected
4
Switch
The DC SWITCH and all other breakers
connected to the inverter are OFF
5
Cable connection
The cables on the AC/PV/battery side are
correctly and securely connected
6
Unused terminals & ports
All unused terminals and ports are sealed
with waterproof caps
7
Installation environment
The installation environment meets all the
requirements specified in this manual and
ensure that the ventilation valve is not
obstructed
7.2 Powering on the system
Ÿ Wear insulated gloves and use insulated tools to avoid electric
shocks or short-circuit accidents.
Ÿ Before turning on the AC breaker, check if the AC voltage is within
the permissible range using a multimeter.
Ÿ After powering on the system, the OLED screen will display the
error code/warning code when a fault/alarm occurs. For detailed
troubleshooting suggestions, please see Section 12
Troubleshooting.
DANGER
Information
Step 1. If the inverter is connected to a battery, turn the DC SWITCH on the battery to
ON.
Step 5. Tap the touch button to view information concerning the inverter on the OLED
screen.
Step 4. Check the running status of the inverter by observing the OLED screen.
Step 2. Set the DC SWITCH on the left side of the inverter to ON.
Step 3. Turn on the AC breaker between the inverter and the grid.
7.3 Setting the country/region
Ÿ For certain models, you need to set the country/area after
powering on the system manually.
Ÿ If a wrong country/area has been selected, you can reconfigure it
in advanced settings. For details, refer to Section 6.4 Setting the
country/area.
5453
Table 7-1 Checking items
Functions 8
8.1 Setting the export limitation
Ÿ To enable export limitation, a smart meter is required. Please
select the meter recommended above; otherwise, the
communication protocol may be mismatched.
Ÿ Please ensure that all cables are correctly connected and the
Export Limitation is enabled.
Note: Setting the following parameters on the ShinePhone APP or
the Server webpage requires the password. To access the
password, please contact Growatt service personnel.
Information
WARNING
8.1.1 On the OLED screen
For details, please see Section 6.6 Setting the export limitation parameters.
8.1.2 On the ShinePhone APP
NOTICE
NOTICE