Fig 5.5
1> As shown in Fig5-8, 4-6 persons lift the inverter out of package, and then use four
carrying handles to move theinverter to installation position.
2> When you are moving the inverter, please keep the balance.
Notice: There will be front and bottom mark on the package.
14
C.When you install multiple inverters on one surface, inverters should be installed as
following drawing. (Choose one of the two options below).
≥1000 ≥1000
≥1000
≥1000
≥1000
unit: mm
Fig 5.6
≥800 ≥800 ≥800
≥600≥600
unit: mm
D.Do not install inverter into an enclosed space like following drawing.
Fig 5.7
5.3 Moving Requirements
• The inverter is heavy, please move it with care and keep balance to avoid
personnel injury.
• Do not place the inverter with its wiring and signal terminals at the
bottom contacting with floor or any other object because the terminals
are not designed to support the weight of inverter.
13
WARNING
Fig 5.8
5.4 Wall Mount Bracket Installation
Before install the inverter you need install the wall mount bracket so that the inverter can
be firmly installed on the wall.
Wall mount plan: