UM Version 1.1 11 GMVGMSGW 1/12
4.3 GMS GW Settings
4.3.1 LCD Menu Interface
Most of the critical configuration parameters of the GMS GW can be revised and changed with
LCD menu interface controlled with buttons.
Up Button
OK
OK Button
Down Button
Exit or Cancel Button
4.3.2 Configuring Device Object’s Instance number
The Device Object's Instance number must be unique across the entire BACnet internetwork
because it is used to uniquely identify the BACnet devices. It may be used to conveniently
identify the BACnet device from other devices during installation.
Press OK to enter Menu
Press Down to select BACnet item
Press OK to enter BACnet item
Press OK to configure Instance number
Up to increase digit value
Down to decrease digit value
OK to change next digit
Exit to store Instance number
Press Exit to return to the upper layer of
the Menu or exit Menu.
Menu will be closed automatically after
10 seconds of inactivity
Device Object’s Instance number change will be effective after restarting the GMS GW.