GMC-I Messtechnik GmbH 7
3.3 Connecting the PRCD
The respective PRCD must be connected to
the test adapter for all tests.
Connecting a Single-Phase PRCD
Insert the earthing contact inlet plug from
the PRCD into the earthing contact out-
let (4) at the test adapter.
Insert the earthing contact plug (2) from
the test adapter into the outlet coupling
socket at the PRCD.
Example of a Single-Phase PRCD
Connecting a 3-Phase PRCD
Insert the CEE inlet plug from the PRCD
into the CEE outlet (6) at the test
adapter.
Insert the CEE plug (1) from the test
adapter into the CEE outlet coupling
socket at the PRCD.
4 Measurements with the
PROFITEST MXTRA
In order to perform protective conductor mea-
surements (Rlo) at
type S PRCDs
with the
PROFITEST
MXTRA
, the test adapter must remain connected
to the mains.
The test adapter can remain connected to the
mains for protective conductor measurements
conducted at PRCDs whose protective conduc-
tor is not switched, as well as for insulation mea-
surements (Rins) with the
PROFITEST MXTRA
4.1 Measuring Protective Conductor
Resistance (Rlo)
As opposed to the usual default setting for
low-resistance measurements, the device
under test does not have to be discon-
nected from all sources of voltage in this
case. Depending on the PRCD, the rotary
selector switches have to be set to the ON
and the 1~ ON or 3~ ON positions, in order to
be able to activate the PRCD and switch the
protective conductor through.
Example of a Single-Phase PRCD
Before performing protective conductor
measurements, execute an offset mea-
surement to assure that the test
adapter’s connector contacts are not in-
cluded in the measurement results.
Insert the respective test plug into the
appropriate socket at the test adapter to
this end: 2 to 4 or 1 to 6.
Start the offset measurement at the
PROFITEST MXTRA
.
Connect the PRCD as described in sec-
tion 3.3.
Connect the PROFITEST MXTRA test instru-
ment to sockets 9 and 10 via the 2-pole
measuring adapter.
PROFITESTPRCD Measurement with the PROFITEST MXTRA