THE INSTRUMENT
19 | 71 ENERGYMID
5.10 CHARACTERISTIC VALUES
5.10.1 MEASURING RANGES
5.10.2 INPUTS, OUTPUTS AND INTERFACES
The energy meters are equipped with two pulse outputs or one bus output depending on model and variant.
5.10.3 TARIFF INPUTS
All instruments are equipped with 4 hardware-controlled tariff inputs. The tariffs are controlled via these tariff inputs by ap-
plying a certain voltage level:
 Level 0 = < 12 V
AC
 Level 1 = 45 … 265 V
AC
Depending on the combination of levels 0 and 1, the values measured at the instrument are recorded in the corresponding
tariff. Recording is thus possible in a daytime and a nighttime tariff, for example.
Instruments with bus (features W1, W2, W4, W7) have 4 additional software-controlled tariffs (not included in the scope of
MID approval). Further information can be found in the respective interface description. See chapter "Bus Connections (fea-
tures W1 / W2 / W4 / W7 / W8)" 52.
The active tariff appears at the display 33.
5.10.4 PULSE OUTPUTS
Pulses are transmitted via the pulse outputs (pulses per kWh). One of 4 pulse sources can be selected for each output: active
energy import, active energy export, reactive energy import or reactive energy export. Pulse frequency and duration can also
be adjusted on some models and variants.
Direct connection: Pulse frequency is proportional to measured energy.
Transformer connection: The permitted energy values are transmitted. In the case of feature Q0 and Q1, these are the sec-
ondary energy values. However, in the case of feature Q9, the primary energy values in consideration of the CT and VT value
are transmitted.
The pulse outputs are electrically isolated from the measuring circuit by means of an optocoupler.
Voltage
Reference voltage U
n
AC: U3: 100 … 110 V L–L
U5 230 V L–N
U6: 400 V L–L
Allowable deviation: -20% … +15%
Current
I
ref
Direct connection:
Transformer connection:
5 A
1 A
Starting current Direct connection:
Transformer connection:
20 mA
2 mA
I
min
Direct connection:
Transformer connection:
0.1 A
0.01 A
I
max
Direct connection:
Transformer connection:
80 A
6 A
Frequency range
Nominal frequency: 50 Hz
Cutoff frequency: 45 Hz … 65 Hz
Accuracy
Active energy: Class B per EN 50470-3
Reactive energy: Class 2 per EN 62053-23
Sampling rate Continuous, 32 per period
Note
Circuit diagrams, terminal assignments etc. can be found under chapter "Initial Startup" 22.