Goodwe GW50K06-ETC handleiding
Handleiding
Je bekijkt pagina 71 van 74

67
10 Technical Parameters
User Manual V1.2-2024-10-30
Technical Data GW50K07-BTC GW50K06-BTC GW100K07-BTC GW100K06-BTC
Inrush Current (Peak
and Duration) (A)
160 NA 320 NA
Maximum Output
Overcurrent
Protection (A)
155 NA 310 NA
Nominal Output
Voltage (V)
400 NA 400 NA
Nominal Output
Freqency (Hz)
50/60 NA 50/60 NA
Output THDv (@Linear
Load)
<3% NA <3% NA
Switching from Grid
Connected Mode to
Standa/lone Mode
<10ms NA <10ms NA
Eciency
Max. Eciency 97.6% 97.6% 97.6% 97.6%
European Eciency 97.3% 97.3% 97.3% 97.3%
Max. Battery to AC
Eciency
97.2% 97.2% 97.2% 97.2%
Protection
Residual Current
Monitoring
Integrated Integrated Integrated Integrated
Battery Reverse
Polarity Protection
Integrated Integrated Integrated Integrated
Anti-islanding
Protection
Integrated Integrated Integrated Integrated
AC Overcurrent
Protection
Integrated Integrated Integrated Integrated
AC Short Circuit
Protection
Integrated Integrated Integrated Integrated
AC Overvoltage
Protection
Integrated Integrated Integrated Integrated
DC Switch Integrated Integrated Integrated Integrated
AC Switch Integrated Integrated Integrated Integrated
AC Surge Protection
Type II(Type I+
II Optional)
Type II(Type I+
II Optional)
Type II(Type I+
II Optional)
Type II(Type I+
II Optional)
Emergency Power O Integrated Integrated Integrated Integrated
Remote Shutdown Integrated Integrated Integrated Integrated
General Data