10 Technical Parameters
User Manual V1.2-2024-10-30
Technical Data GW50K07-ETC GW50K06-ETC GW100K07-ETC GW100K06-ETC
Max. Total Harmonic
Distortion
<3% <3% <3% <3%
Maximum Output
Overcurrent
Protection (A)
155 155 310 310
AC Output Data (Back-up)
Back-up Nominal
Apparent Power (kVA)
50 NA 100 NA
Max. Output Apparent
Power without Grid
(kVA)
55 NA 110 NA
Max. Output Apparent
Power with Grid (kVA)
55 NA 110 NA
Nominal Output
Current (A)
72.5 NA 145.0 NA
Max. Output Current
(A)
79.8 NA 159.5 NA
Max. Output Fault
Current (Peak and
Duration) (A)
155@187.5us NA 310@187.5us NA
Inrush Current (Peak
and Duration) (A)
160 NA 320 NA
Maximum Output
Overcurrent
Protection (A)
155 NA 310 NA
Nominal Output
Voltage (V)
400 NA 400 NA
Nominal Output
Freqency (Hz)
50/60 NA 50/60 NA
Output THDv (@Linear
Load)
<3% NA <3% NA
Switching from Grid
Connected Mode to
Stand/alone Mode
<10ms NA <10ms NA
Eciency
Max. Eciency 97.6% 97.6% 97.6% 97.6%
European Eciency 97.3% 97.3% 97.3% 97.3%
Max. Battery to AC
Eciency
97.2% 97.2% 97.2% 97.2%
MPPT Eciency 99.9% 99.9% 99.9% 99.9%
Protection