09 Maintenance
User Manual V1.2-2024-10-30
No� Fault Cause Solutions
7 GridFreqFault
Utility grid
exception. The
actual grid
frequency exceeds
the requirement
of the local grid
standard.
1. If the problem occurs occasionally, the
utility grid may be abnormal temporarily.
The inverter will recover automatically
after detecting that the utility grid is
normal.
2. If the problem occurs frequently, check
whether the grid frequency is within the
permissible range.
• Contact the local power company if the
grid frequency exceeds the permissible
range.
• Modify the overfrequency protection
threshold or disable the overfrequency
protection function after obtaining the
consent of the local power company
if the grid frequency is within the
permissible range.
8 EepromFault
Data memory
device exception.
Disconnect the AC output switch and DC input
switch, then connect them 5 minutes later.
Contact the dealer or the after-sales service if
the problem persists.