Goodwe GW50K06-ETC handleiding
Handleiding
Je bekijkt pagina 57 van 74

53
09 Maintenance
User Manual V1.2-2024-10-30
On-grid/o-grid switching module fault
No� Fault Cause Solutions
1 HCTCheckFault
The sampling
of the AC HCT is
abnormal.
Disconnect the AC output switch and DC input
switch, then connect them 5 minutes later.
Contact the dealer or the after-sales service if
the problem persists.
2 NoUtility
1. Utility grid
exception.
2. The AC cable is
disconnected, or
the AC breaker is
disconnected.
1. The alarm is automatically cleared after the
grid power supply is restored.
2. Check whether the AC cable is connected
and the AC breaker is on.
3 OverTempFault
1. The inverter is
installed in a
place with poor
ventilation.
2. The ambient
temperature is
too high.
3. A fault occurs in
the internal fan
of the inverter.
1. Check the ventilation and the ambient
temperature at the installation point.
2. If the ventilation is poor or the ambient
temperature is too high, improve the
ventilation and heat dissipation.
3. Contact the dealer or after-sales service
if both the ventilation and the ambient
temperature are proper.
No� Fault Cause Solutions
22 SPIComFault
1. Frame format
error
2. Parity checking
error
3. Can bus oine
4. Hardware CRC
error
5. Send (receive)
control bit is
receive (send).
6. Transmit to the
unit that is not
allowed.
Disconnect the AC output switch and DC
input switch, then connect them 5 minutes
later. Contact the dealer or the after-sales
service if the problem persists.