No. Fault Cause Solutions
4 Grid Undervoltage
The grid voltage is lower
than the allowed range,
or the duration exceeds
the setted value of LVRT
duration.
1. If occurs occasionaly, it may
be caused a short term grid
abnormity. The inverter will recover
automatically after the grid is back
to normal operation.
2. If it occurs frequently, please check
whether the grid voltage is within
the allowed range.
• If the grid voltage exceeds the
allowed range, please contact
local power operator.
• If the grid voltage is within the
allowable range, please modify
the inverter grid undervoltage
protection value with the
consent of the local power
operator.
3. If it does not recover for a long time,
please check whether the AC side
circuit breaker or output cables are
connected properly.
5
Grid 10min
Overvoltage
The average value of
the grid voltage within
10 minutes exceeds the
range specied by safety
regulations.
1. If occurs occasionaly, it may
be caused a short term grid
abnormity. The inverter will recover
automatically after the grid is back to
normal operation.
2. If it occurs frequently, please check
whether the grid voltage is within
the allowed range.
• If the grid voltage exceeds the
allowed range, please contact
local power operator.
• If the grid voltage is within the
allowable range, please modify
the Grid 10min Overvoltage
protection value with the
consent of the local power
operator.
6
Grid
Overfrequency
The frequency of the grid
exceeds the local grid
standard range.
1. If occurs occasionaly, it may
be caused a short term grid
abnormity. The inverter will recover
automatically after the grid is back
to normal operation.
2. If it occurs frequently, please check
whether the grid voltage is within
the allowed range.
• If the grid voltage exceeds the
allowed range, please contact
local power operator.
• If the grid voltage is within
the allowable range, please
modify the Grid Overfrequency
protection value with the
consent of the local power
operator.