04 Check and Storage
14
User Manual V1.2-2025-01-16
4.3 Storage
If the equipment is not to be installed or used immediately, please ensure that the storage
environment meets the following requirements:
1. Do not unpack the outer package or throw the desiccant away.
2. Store the equipment in a clean place. Make sure the temperature and humidity are
appropriate and no condensation.
3. Follow the instructions on the packing box when stacking the inverters. Stack with caution to
prevent them from falling over.
4. If the inverter has been long term stored, it should be checked by professionals before being
put into use.
5. If the inverter has been stored for more than two years or has not been in operation for
more than six months after installation, it is recommended to be inspected and tested by
professionals before being put into use.
6. To ensure good electrical performance of the internal electronic components of the inverter,
it is recommended to power it on every 6 months during storage. If it has not been powered
on for more than 6 months, it is recommended to to be inspected and tested by professionals
before being put into use.
5 Installation
5.1 Installation Requirements
1. Do not install the equipment in a place near ammable, explosive, or corrosive materials.
2. Install the equipment on a surface that is solid enough to bear the inverter weight.
3. Install the equipment in a well-ventilated place to ensure good dissipation. Also, the
installation space should be large enough for operations.
4. The equipment with a high ingress protection rating can be installed indoors or outdoors.
The temperature and humidity at the installation site should be within the appropriate range.
5. Install the equipment in a sheltered place to avoid direct sunlight, rain, and snow. Build a
sunshade if it is needed.
6. Do not install the equipment in a place that is easy to touch, especially within children’s
reach. High temperature exists when the equipment is working. Do not touch the surface to
avoid burning.
7. Install the inverters far away from noise-sensitive areas, such as the residential area, school,
hospital etc., in order to avoid the noises bothering people nearby.
8. Inverters installed in salt-damaged areas may suer from corrosion. Salt-damaged areas
refer to areas within 1000 m of the coast or aected by sea winds. The areas aected by sea
wind vary depending on meteorological conditions (such as typhoons, seasonal winds) or
terrain (with embankments, hills).
9. Install the equipment at a height that is convenient for operation and maintenance, electrical
connections, and checking indicators and labels.
10. Install the inverter away from high magnetic eld to avoid electromagnetic interference.If
there is any radio or wireless communication equipment below 30MHz near the inverter, you
have to:
• Install the inverter at least 30m far away from the wireless equipment.
• Add a low pass EMI lter or a multi winding ferrite core to the DC input cable or AC output
cable of the inverter.
11. Please ensure that there are no obstacles directly in front of the outside fans outlet on the
left side of the inverter so that the outside fans can be drawn out normally.