09 Maintenance
61
No. Fault Cause Solutions
1 Utility Loss
1. Utility grid
power fails.
2. The AC
circuit or the
AC breaker is
disconnected.
1. The alarm will be automatically
cleared after the grid power
supply restores.
2. Check whether the AC cable is
connected and the AC breaker is
on.
2
Grid
Overvoltage
The grid voltage
exceeds the
allowed range,
or the duration
exceeds the set
value of HVRT
duration.
1. If occurs occasionally, it may
be caused a short term grid
abnormality. The inverter will
recover automatically after the
grid is normal.
2. If it occurs frequently, please
check whether the grid voltage is
within the allowed range.
If the grid voltage exceeds the
allowable range, please contact
local power operator.
If the grid voltage is within the
allowable range, please modify
the Grid, HVRT or Overvoltage
protection value with the
consent of the local power
operator.
3. If it does not restore for a long
time, please check whether the
AC side circuit breaker or output
cables are connected properly.