06 Electrical Connection
50
Terminal Port
denition
for model C
Port denition
for model D
Description
remote shutdown/
EPO (Only for
India)
7: DI1-
8: DI+
7: DI1-
8: DI+
The AC side of the inverter is
automatically disconnected
after the emergency swith
gives a shutdown signal,
stopping grid connection. An
external emergency shut-
down switch is required and
controlled through the DI
port:
• Remote Shutdown: if the
DI port is connected, the
machine will be started; if the
DI port is disconnected, the
machine will be stopped.
• Emergency Shutdown: if
DI port is connected, it will
stop the machine; if DI port is
disconnected, it will start the
machine.
Dry contact 1
11: DO1+
12: NA
13: DO1-
11: DO1+
12: NA
13: DO1-
Load control
Dry contact 2
14: DO2+
15: DO2-
12: DO2+
13: DO2-
Load control
Dry contact 3 Reserved
14: DO3+
15: DO3-
Load control
NS protection Reserved Reserved
To connect NS protection
device (Only for Germany).