Goodwe GW50K-SDT-C30 handleiding
Handleiding
Je bekijkt pagina 53 van 127

06 Electrical Connection
49
Terminal Port
denition
for model C
Port
denition for
model D
Description
Meter(Single
inverter)
5: RS485_B2
6: RS485_A2
5: RS485_B2
6: RS485_A2
The inverter is paired with a
meter to achieve the function
of preventing output power
limitation. If you need supporting
equipment, you can contact
the inverter manufacturer for
purchase.
Inverter
1: RS485_B1
2 RS485_A1
1: RS485_B1
2 RS485_A1
To connect with the RS485 port of
multi inverters
or the smart Data Logger.
Ezlogger3000C
(Multiple inverters)
3: RS485_B1
4: RS485_A1
3: RS485_B1
4: RS485_A1
To connect with the RS485 port of
multi inverters
or the smart Data Logger.
RCR/DRED
16: COM/DRM0
17: REFGEN
18: DRM4/8
19: DRM3/7
20: DRM2/6
21: DRM1/5
16: REF_1 or COM/
DRM0
17: REF_2 or
REFGEN
18: DI_4 or DRM4/8
19: DI_3 or DRM3/7
20: DI_2 or DRM2/6
21: DI_1 or DRM1/5
DRED (Demand Response
Enabling Device): It provides
a DRED signal control port to
meet the DRED accreditation in
Australia and other regions.
RCR (Ripple Control Receiver): It
provides an RCR signal control
port to meet the grid dispatching
requirements in regions such as
Germany.
The functions of DRM1-4 are
reserved, and users need to
prepare their own DRM devices.