06 Electrical Connection
48
Terminal Port
denition
for model A
Port denition
for model B
Description
RCR/DRED Reserved
8: REF_1 or COM/
DRM0
9: REF_2 or REFGEN
10: DI_4 or DRM4/8
11: DI_3 or DRM3/7
12: DI_2 or DRM2/6
13: DI_1 or DRM1/5
DRED (Demand Response
Enabling Device): It provides
a DRED signal control port to
meet the DRED accreditation in
Australia and other regions.
RCR (Ripple Control Receiver): It
provides an RCR signal control
port to meet the grid dispatching
requirements in regions such as
Germany.
The functions of DRM1-4 are
reserved, and users need to
prepare their own DRM devices.
remote shutdown/
EPO (Only for
India)
20: DI1-
21: DI+
1: DI1-
2: DI+
The AC side of the inverter is
automatically disconnected
after the emergency swith gives
a shutdown signal, stopping
grid connection. An external
emergency shutdown switch is
required and
controlled through the DI port:
• Remote Shutdown: if the DI
port is connected, the machine
will be started; if the DI port is
disconnected, the machine will
be stopped.
• Emergency Shutdown: if DI port
is connected, it will stop the ma-
chine; if DI port is disconnected,
it will start the machine.
Dry contact 1
5: DO1+
6: NA
7: DO1-
5: DO1+
6: NA
7: DO1-
Load control
Dry contact 2
1: DO2+
2: DO2-
20: DO2+
21: DO2-
Load control
Dry contact 3 Reserved Reserved Load control
NS protection Reserved
3: DI2-
4: DI2+
To connect NS protection device
(Only for Germany).