Goodwe GW10K-MS handleiding
Handleiding
Je bekijkt pagina 53 van 60

10 Technical Parameters
49
User Manual V2.2-2025-07-24
Technical Parameters GW5000-MS-30 GW6000-MS-30 GW7000-MS-30 GW8500-MS-30
AC Grid Frequency
Range (Hz)
45~55 / 55~65 45~55 / 55~65 45~55 / 55~65 45~55 / 55~65
Max. Output Current
(A)
*3
24.0 28.7 33.5 40.7
Max. Output Fault
Current(peak and
duration) (A)
56.5 56.5 77 94
Inrush Current(peak
and duration) (A)
50 50 50 50
Nominal Output
Current (A)
*4
21.8 26.1 30.5 37.0
Power Factor ~1 (Adjustable from 0.8 leading to 0.8 lagging)
Max. Total Harmonic
Distortion
<3%
Maximum Output
Overcurrent Protection
(A)
56.5 56.5 77 94
Eciency
Max. Eciency
*5
97.8% 97.8% 97.7% 97.9%
European Eciency
*6
97.2% 97.2% 97.1% 97.3%
Protection
PV String Current
Monitoring
Integrated
DC Insulation
Resistance Detection
Integrated
Residual Current
Monitoring
Integrated
DC Reverse Polarity
Protection
Integrated
Anti-islanding
Protection
Integrated
AC Overcurrent
Protection
Integrated
AC Short Circuit
Protection
Integrated
AC Overvoltage
Protection
Integrated
DC Switch Integrated
DC Surge Protection Type III(Type II Optional)
AC Surge Protection Type III(Type II Optional)
AFCI Optional
Rapid Shutdown Optional
Bekijk gratis de handleiding van Goodwe GW10K-MS, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
| Merk | Goodwe |
| Model | GW10K-MS |
| Categorie | Niet gecategoriseerd |
| Taal | Nederlands |
| Grootte | 6944 MB |