Goodwe EzLogger3000C handleiding

135 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 66 van 135
08 System Commissioning
61
User Manual V1.2-2025-04-15
8.2.10 Setting Third-Parties Parameters
IEC104 Parameters
Set IEC104 parameters when the EzLogger is connected to a management system through the
IEC104 protocol.
Set the forwarding parameters to forward the data collected by the EzLogger to a third party
management platform.
4
3
2
1
5
6
Parameter Description
Channel Name Dene the device name based on actual needs.
Local IP Set the IP address of the EzLogger.
Local Port Set the port number of the EzLogger.
Default port number: 2404.
Remote IP Set the IP address of the IEC104 management system.
Remote Port
Set the port number of the IEC104 management system. Set it to 0 if the
remote port number is not xed.
Point Table Selection Select the access point table.
ASDU Address
After importing the point table, the point table of the management
system can be mapped when the setting the third party conguration.
Select the parameter based on the actual situation.
Time calibration or
not
Set time calibration with the remote device or not based on actual situ-
ation.