08 System Commissioning
59
User Manual V1.2-2025-04-15
Parameter Description
PU Curve Output
Response Mode
The output response mode of the PU curve. Supported mode: gradient
control or PT-1 behavior.
PU Curve Output
Power Changing
Rate
The power change slope when the PU Curve Output Response Mode is
gradient control.
PU Curve Response
Time Parameter
The response time when the PU Curve Output Response Mode is PT-1
behavior.
QU Curve Enable Enable or disable PU Curve.
Vn Voltage Value
(0.1%)
The percentage of actual voltage to the rated voltage at Vn point, n=1,
2, 3, 4.
Vn Active Power
Value (0.1%)
The percentage of the reactive output power to the apparent power at
Vn point, n=1, 2, 3, 4.
QU Curve Response
Time Parameter
The response time when the QU curve output response Mode is PT-1
behavior.
Enter Curve Power
(0.1%)
When the inverter output reactive power to the rated power ratio is
between the Enter Curve Power and Exit Curve Power, the ratio
meets QU curve requirements.
Exit Curve Power
(0.1%)
cosφ(P) Curve Enable
Bit
Enable or disable cosφ(P) curve.
Point n Power (0.1%)
The percentage of the inverter output active power to the rated power
at point A/B/C/ D/E.
point n cosφ Value
(pf,0.001)
The power factor at point A/B/C/ D/E.
cosφ(P) Curve
Response Time
The response time when the cosφ(P) curve response Mode is PT-1
behavior.
Enter Curve Voltage
(0.1%)
When the grid voltage is between Enter Curve Voltage and Exit Curve
Voltage, the voltage meets Cosφ curve requirements.
Exit Curve Voltage
(0.1%)
When the grid voltage is between Enter Curve Voltage and Exit Curve
Voltage, the voltage meets Cosφ curve requirements.
QP Curve Post
Enable
Enable or disable QP purve.
QP Curve Pn
The percentage of the output active power to the rated power at Pn
point, n=1, 2, 3, 4, 5, 6.
QP Curve Qn
The percentage of the output active power to the rated power at Pn
point, n=1, 2, 3, 4, 5, 6.
QP Curve Output
Response Time
The response time when the QP curve output response Mode is PT-1
behavior.