08 System Commissioning
58
User Manual V1.2-2025-04-15
Parameter Description
ISO Threshold
Setting
To protect the equipment, the inverter performs an insulation im-
pedance check on the input side during self-check at startup. If the
measured value is lower than the set value, the inverter will not connect
to the grid.
NPE Overvoltage
Detection Switch
Enable or disable N-PE overvoltage detection.
N-PE Error
Threshold
Set the N-PE overvoltage alarm threshold.
Active Power
Scheduling
Response Method
Set the active power scheduling response method. Supported meth-
od: gradient control or PT-1 behavior.
0: disable; 1: gradient control; 2: PT-1 behavior tau; 3: PT-1 behavior
respond time.
Gradient of Active
Power
Set the active power change slope.
Active Power
Scheduling LPF Time
Set the low pass ltering time for active power scheduling.
Reactive Scheduling
Response Method
Set the reactive power scheduling response method. Supported
method: gradient control or PT-1 behavior.
0: disable; 1: gradient control; 2: PT-1 behavior tau; 3: PT-1 behavior
respond time.
Gradient of Reactive
Power
Reactive Power Scheduling LPF Time
Set the low pass
ltering time for
reactive power
scheduling
Set the low pass ltering time for reactive power scheduling.
Parameter Description
Power Baseline of
Over Frequency
Derating
The active power of the device will be derated according to a certain
slope when the grid frequency exceeds overfrequency derating limit.
Under Frequency
Loading Reference
Mode
The active power of the device will be derated according to a certain
slope when the grid frequency is lower than underfrequency derating
limit.
Underfrequency
Power Slope
The inverter output active power will change when the utility grid
frequency is lower than the underfrequency limit. Indicates the slope
when the inverter output power decreases.
PU Curve Enable Enable or disable PU curve.
Vn Voltage Value
(0.1%)
The percentage of actual voltage to the rated voltage at Vn point, n=1,
2, 3, 4.
Vn Active Power
Value (0.1%)
The percentage of the output active power to the apparent power at
Vn point, n=1, 2, 3, 4.
Power Adjustment Parameter Setting