06 Electrical Connection
22
User Manual V1.2-2025-04-15
Function Silkscreen Denition
DI1
- REF1 REF1
DI 1 DI1
DI2
- REF1 REF1
DI 2 DI2
DI3
- REF2 REF2
DI 3 DI3
DI4
- REF2 REF2
DI 4 DI4
Function Silkscreen Denition
DI1
- GND GND
DI 1 DI1
DI2
- GND GND
DI 2 DI2
DI3
- GND GND
DI 3 DI3
DI4
- GND GND
DI 4 DI4
Passive dry contact Active wet contact
6.8 Connecting the DI Communication Cable
NOTICE
The EzLogger oers Demand Response Enabling Device(DERD) signal control port, meeting
DRED certication requirements in Australian and other regions.
The EzLogger oers Ripple Control Receiver (RCR) signal control port, meeting require-
ments in German and other regions.
The EzLogger oers Over Voltage Ground Relay(OVGR)/Reverse Power Relay(RPR) signal
control port, meeting the requirements of dierent application scenarios in Japan and
other regions.
The EzLogger can receive passive dry contact signal or active wet contact signal. Supported
voltage range of active contact: 0-12V, and 8-12V means high level.
It is recommended to keep the signal transmission distance within 10 meters.