Model: GVHC & F Hood Cleaning & Maintenance
This section describes general cleaning & maintenance activities for GVH model hoods. Attention to these
procedures will help ensure the hood remains in good operating condition and continues to run efficiently and
safely.
Code officials in some jurisdictions may require that owner/operators maintain an accessible, permanent record of
these equipment inspections and maintenance activities, along with any repairs accomplished.
5. Hood Cleaning & Maintenance
The hood design incorporates interlock switches to ensure that the unit will shutdown when certain conditions exist
that are inconsistent with safe and effective operation. The interlocks should be tested monthly as described below.
Results of these inspections should be recorded in a log maintained by the owner. If problems are detected, contact
GILES or an authorized service provider. NOTE: Anytime the filter access door is opened and reclose, the hood must
be restarted by pressing and momentarily holding the [START] portion (top) of the POWERswitch.
1. Door Test
: Start hood ... with hood running, unlatch and slightly open the filter access door. Confirm that
hood powers OFFwhen door is opened and that appliances under hood turn OFF, or will not turn ON.
2. Baffle Filter Test
: Remove the baffle filter, then close and latch access door. Start hood ... the red [BAFFLE
OR CHARCOAL FILTER MISSING] light should turn ON and the [APPLIANCE POWERED] light should be OFF.
Check to ensure that appliances under hood will not turn ON. Reinstall the baffle filter, see Section 4.02.3.
3. Charcoal Filter Test
: Same procedure as #2 above except remove the charcoal filter, then proceed as
described above. Reinstall the charcoal filter, see Section 4.02.3.
4. E.A.C. Filter Test
: Same procedure as #2 & #3 above except remove the E.A.C.collector cell, close and latch
access door. Start the hood ... verify that [ON] & [WASH] E.A.C. Status Lights come ON, along with the
amber [APPLIANCE POWERED] light. Wait approx. two (2) minutes. A beeping alarm should begin
sounding. In several seconds the [APPLIANCE POWERED] light should turn OFF. Check to ensure that
appliances under hood will not turn ON. Reinstall the E.A.C.cell, see Section 4.02.3.
5. Filter Clogged Test
: Perform this test ONLY after installing a new charcoal filter. Start hood normally and
allow it to run. Use cardboard or other material to completely block the hood exhaust outlet, holding it
firmly in place so that no air is escaping. Within a few seconds, a continuous tone alarm should begin
sounding. The red [BAFFLE OR CHARCOAL FILTER CLOGGED] light should turn ON and the [APPLIANCE
POWERED] light should turn OFF. Check to ensure that appliances under hood will not turn ON. Remove
the obstruction ... the alarm should silence and the [APPLIANCE POWERED]light should turn back ON.
Should any of the tests fail to yield the described results, contact a factoryauthorized service company and have
the unit evaluated and repaired. Call Giles Services at 8005544537 (or email services@gfse.com) for assistance
with locating an authorized service company in your area.
5.01 Monthly Hood Interlock Inspection (Can be Performed by User)