Model: GVHC & FInstallation
* Appliance(s) exceeding 50 Amps must be powered through a circuit separate from the hood and be interlocked
through the hood’s contactor coil.
** Appliance provided and rated separately from Hood.
2.05 Electrical Specifications
• Food service equipment must be properly grounded in accordance with local code, or in the absence of local
code, with the National Electrical Code, ANSI/NFPA 70
. Improper grounding may result in electrical shock to
users.
• Always consult a certified professional electrician, or other qualified service technician, prior to installation to
ensure that electrical circuits to be used are of sufficient rating to power the hood and associated appliance load.
• I
mproper installation, adjustment, alteration, service or maintenance could result in serious injury or possible
death, equipment or property damage, and could void the warranty.
Hood & Appliance** on same 208240V Circuit
Voltage Hz Phase
Field Provided Appliance
Load (Amps)
Hood Load
(Amps)
Branch Circuit Breaker
Hood & Appliance on Same
Circuit
208240 60 1 or 3
0 10.5 5 20
10.6 14.5 5 25
14.6 22.5 5 35
22.6 38.5 5 55
38.6 46.5 5 65
46.7 50* 5 75
Hood Only Appliance on Separate Circuit Interlocked Through Separate Contactor
Voltage Hz Phase
Hood Load
(Amps)
Breaker
208240 60 1 5 10